Appendix
Display
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
PA4: DHW heating
Display
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
112
EB 5179 EN
Parameter designation
Range of values (default settings)
Copy times-of-use of HK2 for HK3
Only in systems Anl 3, 6
Parameter designation
Range of values (default settings)
DHW demand ON
˚C
20 to 90 °C (40 °C)
Systems with a storage sensor SF1
Co4 -> Fb02 = ON , Fb02 = OFF
Hysteresis
0 to 30 °C (5 °C)
DHW demand ON
˚C
20 to 90 °C (40 °C)
Systems with two storage sensors SF1 and SF2
Co4 -> Fb02 = ON , Fb02 = ON