Samson TROVIS 5179 Mounting And Operating Instructions page 131

District heating controller
Table of Contents

Advertisement

PA1 to PA3: Heating circuits HK1 to HK3
Parameters
Gradient, flow
Level, flow
Maximum flow temperature
Minimum flow temperature
Set-back difference
Gradient, return flow
Level, return flow
Outdoor temperature; point 1
Outdoor temperature; point 2
Outdoor temperature; point 3
Outdoor temperature; point 4
Flow temperature; point 1
Flow temperature; point 2
Flow temperature; point 3
Flow temperature; point 4
Return flow temperature; point 1
Return flow temperature; point 2
Return flow temperature; point 3
Return flow temperature; point 4
Set-back temperature; point 2
Set-back temperature; point 3
Day set point
Night set point
Sustained temperature
Maximum return flow temperature
Minimum return flow temperature
OT activation value rated operation
OT deactivation value
reduced operation
OT deactivation value
rated operation
PA1
PA2
PA3
Range of values
0.4 to 3.2
–30 to 30 °C
20 to 130 °C
20 to 130 °C
0 to 50 °C
0.4 to 3.2
–30 to 30 °C
–30 to 90 °C
–30 to 90 °C
–30 to 90 °C
–30 to 90 °C
20 to 130 °C
20 to 130 °C
20 to 130 °C
20 to 130 °C
20 to 90 °C
20 to 90 °C
20 to 90 °C
20 to 90 °C
0 to 50 °C
0 to 50 °C
10 to 90 °C
10 to 90 °C
10 to 90 °C
20 to 90 °C
20 to 90 °C
–30 to 50 °C
–10 to 50 °C
0 to 90 °C
EB 5179 EN
Appendix
131

Advertisement

Table of Contents
loading

Table of Contents