Operation

1.6.2 Entering public holidays

On public holidays, the times-of-use specified for Sunday apply. A maximum of 20 public holi-
days may be entered.
Parameters
Public holidays f. heating circuit 1
Public holidays f. heating circuit 2
Public holidays f. heating circuit 3
Note!
The programmed public holidays and vacations of any heating circuit (HK1, HK2 or HK3) ap-
ply with the setting Co4 -> Fb12 = ON , select 1, 2 or 3 also for the DHW heating.
Proceed as follows:
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
To enter additional public holidays, re-select – – – – (between 31.12 and 01.01) and repeat the
steps in the fields highlighted in gray.
Exit the parameter level.
Return to the operating level.
16
EB 5179 EN
WE
Level / Range of values
PA1 / 01.01 to 31.12
PA2 / 01.01 to 31.12
PA3 / 01.01 to 31.12
Switch to configuration and parameter level.
Display: PA1
Select parameter level.
Open parameter level.
Select datapoint for public holidays.
Display shows:
Open data point for public holidays.
If applicable, select – – – – .
Activate editing mode for public holiday.
blinks.
Edit public holiday
Confirm public holiday.