12.5 Technical data

Inputs
Sensor inputs
Binary inputs
Other inputs
Outputs
Analog output
Control signal y
Binary outputs
Operating voltage
Interface
Ambient temperature
Storage temperature
Degree of protection
Class of protection
Degree of contamination
Overvoltage category
Humidity rating
Noise immunity
Noise emission
Weight
Max. 17 configurable inputs for temperature sensors
Pt 100, Pt 1000, Ni 200, Ni 1000 und PTC, NTC, 0–10 V, 0/4–20 mA
or binary alarms (heating/DHW circuit)
5 flow temperature sensors,
2 outdoor temperature sensors,
2 return flow temperature sensors,
2 room temperature sensors,
2 storage tank temperature sensors
Storage tank thermostat
Pulse counter input for flow rate or capacity limitation
Inputs for valve position feedback, remote operation to correct the
room temperature and to select the operating mode
3 outputs
0 to 10 V (load > 4.7 kΩ)
Three-step signal: 230 V~, 2 A
On/off signal: 230 V~, 2 A
5 outputs to control pumps, 230 V~, 3 A
4 outputs for alarms max. 50 V DC, 100 mA
230 V, 48 to 62 Hz, 8 VA
RS-232 for connection to a modem, interface for meter bus
LON (free topology)
0 to 40 °C
–20 to 60 °C
IP 40 according to IEC 529
II according to VDE 0106
2 according to VDE 0110
II according to VDE 0110
F according to VDE 40040
According to EN 61000-6-1
According to EN 61000-6-3
Approx. 0.6 kg