Appendix
Display
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
108
EB 5179 EN
Parameter designation
Range of values (default settings)
4-point characteristic
Point 1: Flow temperature
Flow temperatures of the points 2, 3, 4 are marked by squares
below the numbers 2, 3, 4.
20 to 130 °C
(point 1 = 70 °C, point 2 = 55 °C, point 3 = 40 °C, point 4 = 25 °C)
4-point characteristic
Point 1: Return flow temperature
Return flow temperatures of the points 2, 3, 4 are marked by
squares below the numbers 2, 3, 4.
20 to 90 °C
(point 1 = 65 °C, point 2 = 50 °C, point 3 = 35 °C, point 4 = 20 °C)
4-point characteristic Set-back difference
Varying set-back differences can be entered for the second and
third points. The corresponding point is marked by squares below
the numbers 2 and 3.
0 to 50 °C (20 °C)
Maximum flow temperature
˚C
20 to 130 °C (90 °C)
Minimum flow temperature
˚C
20 to 130 °C (20 °C)
Control according to fixed set point:
Min. return flow temperature = Max. return flow temperature