System-wide functions
Settings for flow rate limitation
Functions
Limitation of heat meter (WMZ)
Pulse input for flow rate or capacity limitation
Parameters
Maximum flow rate of the entire system
Maximum flow rate of the DHW heating
Proportional-action coefficient for the limitation
Select CONST additionally for:
Maximum flow rate of the heating
Select 4-Pt additionally for:
Outdoor temperature Point 1
Maximum flow rate limitation, points 1 to 4
A second pulse counter can be connected at terminal 29. The pulses entered are stored in the
holding registers 40031 (low byte) and 40032 (high byte). The associated duration on the
holding registers 40035 (low byte) and 40036 (high byte). First, the low byte counts upwards
(0 to 65535). If several pulses arrive, the counting value is formed by multiplying the low byte
with the high byte (32-bit value).

7.12 Locking manual level

To protect the heating system, this function can be used to lock manual level. When this function
has been activated, automatic mode is started when the rotary switch is set to +, – or 0.
Function
Locking manual levels
66
EB 5179 EN
Point 2
Point 3
Point 4
WE
Configuration
OFF
Co5 -> Fb08 = OFF
OFF
Co5 -> Fb09 = ON, select: U
CONST:
4-Pt:
10
Pulse weighting / 0.1 to 10
WE
Parameter level / Range of values
3
9 m
/h
PA5 / 0.01 to 99.9 m
3
9 m
/h
PA5 / 0.01 to 99.9 m
1.0
PA5 / 0.1 to 10
3
9 m
/h
PA5 / 0.01 to 99.9 m
–15 °C
PA5 /–30 to 90 °C
– 5 °C
5 °C
15 °C
3
9 m
/h
PA5 / 0.01 to 99.9 m
WE
Configuration
OFF
Co5 -> Fb10 = ON
Limitation constant
Limitation acc. to
4-point characteristic
3
/h
3
/h
3
/h
3
/h