Appendix
Fb Function
09 RK switched off
when switch at
MAN-CLOSED
10 4-point character-
istic
11 Summer mode
12 Potentiometer input
Release HK
13 Pump
management
14 Continuous-action
control for heating
circuit
15 Three-step control
for heating circuit
16 Parameter
optimization
98
EB 5179 EN
Comments
WE
Anl
Function block parameters / Range of values (default settings)
OFF
All
Co1, 2, 3 -> Fb09 = ON: UP still runs until 1 x T
The flow sensor is no longer be read.
OFF
Not
Co1, 2, 3 -> Fb10 = ON: 4-point characteristic
3, 5,
Co1, 2, 3 -> Fb10 = OFF: Gradient characteristic
8, 10
ON
All
Co1, 2, 3 -> Fb11 = ON: Function block parameters:
Start summer mode / 01.01 to 31.12 (01.05)
End summer mode/ 01.01 to 31.12 (30.09)
Outdoor temp. limit for summer mode / 0 to 30 °C (18 °C)
OFF
All
Co1, 2, 3 -> Fb12 = ON: Valve position feedback
(0 to 1000 Ω), 1000 Ω additional resistor required
Co1, 2, 3 -> Fb12 = OFF: RK released with binary signal;
Option
With FrG-A:RLG:
OFF
All
Co1, 2 -> Fb13 = ON: BA 2, 4 OFF outside time-of-use
Co1, 2 -> Fb13 = OFF: BA 2, 4 ON outside time-of-use
OFF
All
Co1, 2, 3 -> Fb14 = ON: Continuous-action control 0 to 10 V
Function block parameters:
K
(proportional gain) / 0.1 to 50.0 (0.5)
P
T
(reset time) / 1 to 999 s (200 s)
N
T
(derivative-action time) / 0 to 999 s (0 s)
V
ON
All
Co1, 2, 3 -> Fb15 = ON: Three-step control;
Function block parameters:
K
(proportional gain) / 0.1 to 50.0 (0.5)
P
T
(reset time) / 1 to 999 s (200 s)
N
T
(valve transit time) / 15 to 240 s (120 s)
Y
UP lag time / 120 to 1200 s (240 s)
Co1, 2, 3 -> Fb15 = OFF: On/off control
Function block parameters:
Hysteresis / 1 to 30 °C (5 °C)
Min. activation time / 0 to 600 s (120 s)
Min. deactivation time / 0 to 600 s (120 s)
UP lag time / 120 to 1200 s (240 s)
OFF
6, 9
Co1, 2, 3 -> Fb16 = ON: Automatic parameter optimization
(K
, T
, T
P
N
FrG-E: Released over bin. signal (potentiometer)
FrG-A: Released over time schedule
Configuration acc. to input
FREE:
Input freely available
)