PROFIBUS communication
B.6 Diagnostics
B.5

Output Data (from Master to Slave)

The output data consist per totalizer (net, forwards and reverse) of one byte of which only the
two LSBs respectively are evaluated. All other bits are not evaluated but should be set to 0 for
safety. This value represents the "SET_TOT" parameter of the "Totalizer Function Block" defined
in the PROFIBUS-PA profile.
Table B-8
Bit
1
0
0
1
The transferred value is effective until it is changed, i.e. after the value 1 (reset totalizer) is sent,
for example, the totalizer will remain on the value 0 until the SET_TOT parameter is changed
again.
Each SET_TOT value affects the corresponding totalizer independently of the others. The
quantities are also cumulated independently of each other, i.e. the net quantity does not have
to be equal to the sum of the quantity forwards and quantity reverse especially if a totalizer has
been reset or was preset.
B.6

Diagnostics

The diagnostic data can be requested with the Slave_Diag service. If extended diagnostic
messages exist, this is displayed with the Diag_Flag of the Data_Exchange service. If the master
then calls the Slave_Diag service, the user diagnostic data are supplied in the following form:
Table B-9
Format of complete diagnostic data
Byte
Profile designation
No.
1
Header
2
3
4
5
Diagnosis
6
7
8
The total length of the external diagnostic data is always 8 including the header.
The Diag_Flag is always set when the last 4 bytes of the diagnostic data (corresponds with the
DIAGNOSIS parameter) have changed since the last message therefore also, for example, when
the diagnostic messages disappear again so that the master register each change in the
diagnostic data.
94
Totalizer mode "SET_TOT"
Bit
Profile description
0
0
cancel
1
reset
0
preset
Value
8 (dec.)
254 (dec.)
1
0 or 1
Byte 1
(s. below)
Byte 2
--
Byte 3
--
Byte 4
(s. below)
Meaning
totalizer is running
totalizer is stopped and reset to 0
Totalizer is stopped and reset to a preset value (PRE‐
SET_TOT parameter, only acyclic access)
Meaning
(fixed) length of diagnostic data (number of bytes)
(fixed)
(fixed)
or1 Display of changes in diagnostic data (see below)
Diagnostic information
(not supported)
(reserved)
More diagnosis data is available
Operating Instructions, 09/2021, A5E02225054-AD