Advertisement

Note
Limit bits can only be clearly evaluated in combination with the quality information!
Status byte combinations
The following combinations of the values of the status bytes described above are possible in
normal operation (i.e. when the input value of the function block concerned incl. status is not
simulated:
Table B-7
Valid combinations of the status byte
Value hex
quality
1F
bad
0F
bad
0C
bad
11
bad
07
bad
00
bad
52
uncertain
51
uncertain
4F
uncertain
4B
uncertain
47
uncertain
8E
good
8D
good
8A
good
89
good
84
good
80
good
Note
The status conditions have decreasing priority from top to bottom. If several status conditions
are fulfilled, the current status with the highest priority will be signaled.
SITRANS FUS060 with PROFIBUS PA
Operating Instructions, 09/2021, A5E02225054-AD
Meaning substatus
out of service
device failure
device failure
sensor not connected
configuration error
non specific
sensor conversion not accurate
sensor conversion not accurate
initial value
substitute set
last usable value
active critical alarm
active critical alarm
active advisory alarm
active advisory alarm
active update event
O.K.
PROFIBUS communication
applies to
limits
flow
constant
X
constant
X
O.K.
constant
constant
X
O.K
X
high limited
X
low limited
X
constant
X
constant
X
constant
X
High limited
X
low limited
X
high limited
X
low limited
X
O.K.
X
O.K.
X
B.4 Status bytes
total net
total
total
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
93