Siemens SITRANS FUS060 Operating Instructions Manual page 117

Ultrasonic flowmeters with profibus pa
Hide thumbs Also See for SITRANS FUS060:
Table of Contents

Advertisement

Menu
Device function,
code
Parameters
7.1.3.2.
Engr.unit
1
7.1.3.2.
Roughness
2
7.1.4
Tracks
7.1.4.1
Track 1
7.1.4.1.
Length 1
1
7.1.4.1.
Angle 1
2
7.1.4.1.
Displacement 1
3
7.1.4.1.
Trig. con 1 Up
4
7.1.4.1.
Trig. con 1 Dw
5
7.1.4.1.
AUTO cal. 1
6
7.1.4.1.
WET cal. 1
6
SITRANS FUS060 with PROFIBUS PA
Operating Instructions, 09/2021, A5E02225054-AD
Description
Unit selection (mm or in)
Roughness of the inner pipe wall
(mm or in); for example 0.04 m for
steel pipes
Length of path 1 (m). The distance
between the two ultrasonic transduc‐
ers of path 1, see Figure 7-6 Sensor
geometry data (Page 70).
Angle of path 1
Displacement of path 1 (m)
Note: The value must be smaller than
the half entered pipe diameter (see
menu 7.1.3.2.2).
For 1-path the value must be set to 0
The signal trigger constant of the first
path up.
The signal trigger constant of the first
path down.
The AUTO calibration factor is auto‐
matically calculated
Note: Only shown if AUTO is selected
in menu 7.1.1
The WET calibration factor of the
path.
Note: Only shown if WET is selected
in menu 7.1.1
D.1 Menu items (FW Rev. 4.00.00)
Factory setting
Setting options
mm
mm
in
0.4 mm (0.015748
0.01 to 10.0 mm
in)
Depending of sensor
>0 to 8.0 m
size selected at order‐
ing
Depending of sensor
0 to 89°
size selected at order‐
ing
Depending of sensor
0 to 1.5 m
size selected at order‐
ing
SONO 3100 and SO‐
-1.40 to +1.40
NOKIT:
-0.75
SONO 3100 (special
applications):
Depending on the or‐
dered system
SONO 3300:
Depending on the or‐
dered sensor
SONO 3100 and SO‐
-1.40 to +1.40
NOKIT:
-0.75
SONO 3100 (special
applications):
Depending on the or‐
dered system
SONO 3300:
Depending on the or‐
dered sensor
Depending on facto‐
0.0000010 to
ry calibration of the
100.0000000
transmitter, which is
(value with 7 frac‐
typically done to‐
tional digits)
gether with the or‐
dered sensor
HMI menu structure
Read
or write
Write
Write
Write
Write
Write
Write
Write
Read
Write