Totalizers can also be preset to lower values <>0 (PRESET_TOT parameter) using PROFIBUS.
All totalizers can be set at the same time in menu 1.3.4.
Units for totalizers (menus 3.4.1, 3.5.1 and 3.6.1)
The units can be entered separately for each totalizer. When there is a switchover between mass
and volume flow (by switching between massflow unit and volumeflow unit in menu 3.1.4), the
totalizer readings will automatically be converted according to the density entered in menu
3.1.4. The unit is also automatically converted to the unit last set for the corresponding type
(volume or mass).
Note
The selected display unit is also the unit on the fieldbus output.
("Transducer_Block" and "Function_Block" will have the same unit).
Limits (menus 3.4.2, 3.4.3, 3.5.2, 3.5.3, 3.6.2 and 3.6.3)
The same instructions apply to limits with quantity totalizers as to the output scales (see above).
Totalizer readings and assigned limit values should also be considered according to positive (Hi
limit alarm value is greater than the Lo alarm limit value) or negative sign (Lo limit alarm value
is greater than the Hi alarm limit value)!
The hysteresis is only evaluated with the net totalizer as value fluctuations are only possible
there.
7.4

Device outputs (menu 4)

In these menus the two device outputs (PROFIBUS PA output and digital output 1) are
parameterized.
The PROFIBUS PA output (terminals 7+ and 8-) can indicate flow, sound velocity and US-
amplitude.
The digital output 1 (terminals 5+ and 6-) can indicate pulse, frequency, alarm, status and limits.
PROFIBUS (menu 4.1)
(Terminals 7+ and 8-)
In this menu the PROFIBUS address of the device can be set.
Bus Address (menu 4.1.1)
Any address in the range 1 to 125 is possible in principle. The master on the PROFIBUS recognizes
that an address has not been specifically issued to this device from the factory setting 126. We
recommend setting an address > 30 for SITRANS FUS060 as addresses below 30 are normally
issued to masters. Each address on the PROFIBUS may only be issued once.
SITRANS FUS060 with PROFIBUS PA
Operating Instructions, 09/2021, A5E02225054-AD
Functions
7.4 Device outputs (menu 4)
59