Siemens SITRANS FUS060 Operating Instructions Manual page 26

Ultrasonic flowmeters with profibus pa
Hide thumbs Also See for SITRANS FUS060:
Table of Contents

Advertisement

Description
3.5 PROFIBUS communication
The following functions are implemented in addition to the standard device according to the
PROFIBUS device profile:
• User-specific scaling of all measured variables in the form of a linear representation between
any range of the measured variable ("measuring scale") and the actual output variable
("output scale").
• A measuring range does not need to be set, the valid measuring range is only limited by the
respective sensor limits (see chapter below).
• Upper and lower warning limit for each measured variable to supplement the existing alarm
limits.
• Upper and lower warning and alarm limits for each totalizer, with selectable hysteresis for the
net totalizer.
The following functions on the standard device with 20 mA / HART interface are not available on
the PROFIBUS version as they can generally be replaced indirectly by the PROFIBUS functions.
• Analog output (4 to 20 mA)
• HART communication
• Digital output 2 (relay output)
26
SITRANS FUS060 with PROFIBUS PA
Operating Instructions, 09/2021, A5E02225054-AD