Siemens SITRANS FUS060 Operating Instructions Manual page 109

Ultrasonic flowmeters with profibus pa
Hide thumbs Also See for SITRANS FUS060:
Table of Contents

Advertisement

Menu
Device function,
code
Parameters
3.1.2
Max. vol. flow
3.1.3
Limits
3.1.3.1
Lo alarm limit
3.1.3.2
Hi alarm limit
3.1.3.3
Hysteresis
3.1.4.
Density
Units
Density
3.1.5
Direction
3.1.5.1
Direction
3.1.5.2
Measurement
3.1.5.3
Hysteresis
3.1.6
Low flow cut
3.1.7
Flow damping
3.1.8
Time constant
3.2
Sound velocity
3.2.1
Dynamic range
3.2.2
Dynamic range
3.2.2.1
Lower value
3.2.3
Limits
3.2.3.1
Lo alarm limit
SITRANS FUS060 with PROFIBUS PA
Operating Instructions, 09/2021, A5E02225054-AD
Description
Full scale value
Note: Corresponds to 20 mA and se‐
lected max. frequency
Flow unit according to menu 3.1.1
Lower alarm limit (lower limit must
be lower than upper limit)
High alarm limit (higher limit must
be higher than lower limit)
Hysteresis for limit in % of full scale
value
Density of media
Density unit
Input of density value for arithmetic
calculation of mass flow
Determination of main direction of
flow (forward direction)
Choice of measurement direction
Setting hysteresis for flow direction
related to full scale value
Determination of switching point for
low flow cut-off. Suppression is rela‐
ted to full scale value
Selection of time constants for meas‐
uring variables
Unit for sound velocity
Lower range value for sound velocity
Lower range value
< Upper range value
Lower alarm limit
Lower alarm limit
< Upper alarm limit
D.1 Menu items (FW Rev. 4.00.00)
Factory setting
Setting options
Depends on sensor
See dimension table
size
in sensor manual;
max. 12 m/s
Depends on sensor
See dimension table
size
in sensor manual
Depends on sensor
See dimension table
size
in sensor manual
1%
0% to 20% of Max.
vol. flow setting
(menu 3.1.2)
kg/m³
g/cm³
g/l
kg/l
kg/m³
lb/ft³
lb/in³
lb/gal
lb/lmpgal
+1000.00 kg/m
3
200 to 5000 kg/m
+ Direction
+ Direction
- Direction
Forward only
Forward only
Forward + reverse
1%
0 to 20%
1%
0 to 20%
5.0 sec
0.0 to 200 sec
m/s
m/s
+600 m/s
+200 to 2000 m/s
+200 m/s
200 to 2000 m/s
HMI menu structure
Read
or write
Write
Write
Write
Write
Write
3
Write
Write
Write
Write
Write
Write
Read
Write
Write
109