Establishing Multidrop Communication - Emerson Rosemount 2051 Reference Manual

Pressure transmitter with hart revision 5 and 7 selectable protocol
Hide thumbs Also See for Rosemount 2051:
Table of Contents

Advertisement

Configuration
September 2020
Continuous (same as HART5 burst mode)
Rising
Falling
Windowed
On Change
Note
Consult your host system manufacturer for burst mode requirements.
2.10.4
Configuring burst mode using a Field Communicator
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
2.10.5
Configuring burst mode using AMS Device Manager
Procedure
1. Right select on the device and select Configure.
2. Select the HART tab.
3. Enter the configuration in Burst Mode Configuration fields.
2.11

Establishing multidrop communication

Multidropping transmitters refers to the connection of several transmitters to a single
communications transmission line. Communication between the host and the
transmitters takes place digitally with the analog output of the transmitters deactivated.
Multidrop installation requires consideration of the update rate necessary from each
transmitter, the combination of transmitter models, and the length of the transmission
line. Communication with transmitters can be accomplished with HART
host implementing HART protocol. Each transmitter is identified by a unique address and
responds to the commands defined in the HART protocol. Field Communicators and AMS
Device Manager can test, configure, and format a multidropped transmitter the same way
as a transmitter in a standard point-to-point installation.
Figure 2-18
installation diagram.
34
2, 2, 5, 3
shows a typical multidrop network. This figure is not intended as an
Reference Manual
00809-0100-4107
®
modems and a
Rosemount 2051 Pressure Transmitter

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents