Configuration
September 2020
Procedure
Follow the screen prompts to configure Scaled Variable.
a) When configuring for level, select Linear under Select Scaled data options.
b) When configuring for flow, select Square Root under Select Scaled data options.
Configuring scaled variable using AMS Device Manager
Procedure
1. Right select on the device and, select Configure.
2. Select the Scaled Variable tab and select the Scaled Variable button.
3. Follow screen prompts to configure Scaled Variable
Configuring scaled variable using a LOI
Refer to
Figure 2-14: Configuring Scaled Variable Using a LOI
28
a) When configuring for level applications, select Linear under Select Scaled
data options.
b) When configuring for flow applications, select Square Root under Select
Scaled data options.
Figure 2-14
for instructions to configure Scaled Variable using a LOI.