Emerson Rosemount 2051 Reference Manual page 105

Pressure transmitter with hart revision 5 and 7 selectable protocol
Hide thumbs Also See for Rosemount 2051:
Table of Contents

Advertisement

Reference Manual
00809-0100-4107
6.7.1
Attaching electronics board
Procedure
1. Remove the cable connector from its position inside of the internal black cap and
2. Using the two captive screws as handles, insert the electronics board into the
3. Tighten the captive mounting screws.
4. Replace the housing cover. It is recommended the cover be tightened until there is
6.7.2
Installing terminal block
Procedure
1. Gently slide the terminal block into place, making sure the two power posts from
2. Tighten the captive screws.
3. Replace the electronics housing cover. The transmitter covers must be fully
6.7.3
Reassembling the 2051C process flange
Procedure
1. Inspect the sensor module PTFE O-rings. Undamaged O-rings may be reused.
2. Install the process connection. Possible options include:
Reference Manual
attach it to the electronics board.
housing. Make sure the power posts from the electronics housing properly engage
the receptacles on the electronics board. Do not force. The electronics board should
slide gently on the connections.
no gap between the cover and the housing.
the electronics housing properly engage the receptacles on the terminal block.
engaged to meet Explosion-Proof requirements.
Replace O-rings that show any signs of damage, such as nicks, cuts, or general wear.
Note
If you are replacing the O-rings, be careful not to scratch the O-ring grooves or the
surface of the isolating diaphragm when removing the damaged O-rings.
a) Coplanar process flange:
Hold the process flange in place by installing the two alignment screws to
finger tightness (screws are not pressure retaining). Do not over-tighten
as this will affect module-to-flange alignment.
Install the four 1.75-in. flange bolts by finger tightening them to the
flange.
b) Coplanar process flange with flange adapters:
Hold the process flange in place by installing the two alignment screws to
finger tightness (screws are not pressure retaining). Do not over-tighten
as this will affect module-to-flange alignment.
Troubleshooting
September 2020
105