Reference Manual
00809-0100-4107
To zero the Rosemount 2051, first close the block valve on the low pressure (downstream)
side of the transmitter.
Note
Do not open the low side equalize valve before the high side equalize valve. Doing so will
overpressure the transmitter.
Open the equalize valve on the high pressure (upstream) side of the transmitter.
Reference Manual
H
(Plugged)
Equalize
Equalize
(closed)
(closed)
Isolate
(open)
Process
Drain vent
(closed)
H
(Plugged)
Equalize
Equalize
(closed)
(closed)
Isolate
(open)
Process
Drain vent
(closed)
H
(Plugged)
Equalize
Equalize
(open)
(closed)
Isolate
(open)
Process
Drain vent
(closed)
Hardware Installation
September 2020
L
(Plugged)
Isolate
(open)
Process
L
(Plugged)
Isolate
(closed)
Process
L
(Plugged)
Isolate
(closed)
Process
53