Configuration
September 2020
Performing an analog loop test using AMS Device Manager
Procedure
1. Right select on the device and, within the Methods drop down menu, move cursor
2. Select Next after setting the control loop to manual.
3. Follow Screen prompts to perform a Loop Test.
4. Select Finish to acknowledge the method is complete.
Performing analog loop test using a LOI
To perform an analog loop test using the LOI, the 4 mA (1 V), 20 mA (5 V), and custom mA
point may be set manually. Reference
transmitter loop test using an LOI.
Figure 2-17: Performing an Analog Loop Test Using an LOI
2.9.3
Simulate device variables
It is possible to temporarily set the Pressure, Sensor Temperature, or Scaled Variable to a
user-defined fixed value for testing purposes. Once the simulated variable method is left,
the process variable will be automatically returned to a live measurement. Simulate device
variables is only available in HART
Simulate digital signal with a Field Communicator
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
Simulate digital signal with AMS Device Manager
Procedure
1. Right select on the device and select Service Tools.
2. Select Simulate.
3. Under Device Variables select a digital value to simulate.
32
over Diagnostics and Test. In the Diagnostics and Test drop down menu select Loop
Test.
a) Pressure
Figure 2-17
for instructions on how to perform a
®
Revision 7 mode.
3, 5
Reference Manual
00809-0100-4107
Rosemount 2051 Pressure Transmitter