7.5.4
SIS reference
The product must be operated in accordance to the functional and performance
specifications provided in the
7.5.5
Failure rate data
The FMEDA Report
7.5.6
Failure values
Safety accuracy: ±2.0 percent
Transmitter response time: 1.5 seconds
Self-diagnostics test: At least once every 60 minutes
7.5.7
Product life
50 years - based on worst case component wear-out mechanisms - not based on wear-out
of process wetted materials
Reference Manual
Product Data
Sheet.
includes failure rates and common cause Beta factor estimates.
Safety Instrumented Systems Requirements
September 2020
111