Emerson Rosemount 2051 Reference Manual page 30

Pressure transmitter with hart revision 5 and 7 selectable protocol
Hide thumbs Also See for Rosemount 2051:
Table of Contents

Advertisement

Configuration
September 2020
particular example, the low flow cutoff value is 1000 gallons of water per hour. Based on
this information, the Scaled Variable configuration would be as follows:
Table 2-8: Scaled Variable Configuration for Flow Application
Scaled Variable units:
Scaled data options:
Pressure value position 2:
Scaled Variable position 2:
Low Flow Cutoff:
Note
Pressure value position 1 and Scaled Variable position 1 are always set to zero for a flow
application. No configuration of these values is required.
2.8.3
Re-mapping device variables
The re-mapping function allows the transmitter primary, secondary, tertiary, and
quaternary variables (PV, 2V, 3V, and 4V) to be configured as desired. The PV can be
remapped with a Field Communicator, AMS Device Manager, or a LOI. Variables (2V, 3V,
and 4V) can only be re-mapped via Field Communicator or AMS Device Manager.
Note
The variable assigned to the primary variable drives the 4–20 mA (1–5 Vdc) output. This
value can be selected as Pressure or Scaled Variable. The 2, 3, and 4 variables only apply if
HART
Re-mapping using a Field Communicator
From the HOME screen, enter the Fast Key sequence.
Fast Keys
Re-mapping using AMS Device Manager
Procedure
1. Right select the device and select Configure.
2. Select Manual Setup and click on the HART tab.
3. Assign Primary, secondary, tertiary, and quaternary variables under Variable
4. Select Send.
5. Carefully read the warning and select Yes if it is safe to apply the changes.
Re-mapping using LOI
Refer to
30
®
burst mode is being used.
2, 1, 1, 3
Mapping.
Figure 2-16
for instructions to remap the primary variable using a LOI.
gal/h
square root
125 inH
O
2
20,000 gal/h
1000 gal/h
Reference Manual
00809-0100-4107
Rosemount 2051 Pressure Transmitter

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents