Installation and Operation Guide SOLECTRIA® PVI 25TL-208, PVI 50TL-480 and PVI 60TL-480
WARN0030
(EEPROMERR)
WARN0050
(TEMPSENSORER
R)
PROTECT0090
(BUS OVER
VOLTAGE)
PROTECT0070
(BUS
IMBALANCE)
DOCR-071030-A (10/7/2022)
1. Observe for 5 minutes and see whether the alarm will stop
automatically.
2. Contact after-sales technical support team.
WARNING
Definition:
Internal alarm
Possible causes:
Internal memory has a problem.
Recommended solutions:
1. Observe for 5 minutes and see whether the alarm will stop
automatically.
2. Contact the post-sales technical support team.
Recommended solutions:
1. Observe temperature display.
2. Switch off external AC disconnect, then back on to reboot the
system.
3. Contact the technical support team.
PROTECTION
Recommended solutions:
1. Restart inverter by turning both AC and DC switches OFF. Wait for
1 minute for all energy to discharge and turn both switches ON.
2. If inverter cannot clear fault, replace inverter.
Recommended solutions:
1. Raise limit of IDCmax (for example, 400mA) to allow inverter more
room to adjust in transient condition to cope with imbalance of
impedance and voltage between grid phases.
Page 104 of 131