YASKAWA Solectria PVI 25TL-208 Installation And Operation Manual page 71

Commercial 1000vdc string inverters
Table of Contents

Advertisement

Installation and Operation Guide SOLECTRIA® PVI 25TL-208, PVI 50TL-480 and PVI 60TL-480
 Choosing the communication data. From the previous menu, press ESC to return to the System
Parameters menu. Scroll to Communication Setting and press ENT. Select Baud rate and press ENT. The
default setting is 9600. Depending on the data acquisition/SCADA system being used, the baud rate may
need to be increased or decreased. Scroll up/down to select other speeds and press ENT.
Next, select Address and press ENT. This designates the inverter address. Each inverter within the Modbus
network must have a unique address (Unit ID). Scroll up/down to choose an address for the inverter and
press ENT. Addresses can be assigned from 1-128. See Figure 5-4.
 Setting the LCD contrast grade. From the previous menu, press ESC to return to System Parameters menu.
Select LCD Contrast Setting and press ENT. Using the up/down arrows increase or decrease the contrast
to the desired setting. Press ENT to accept the changes.
 When the LCD screen shows the normal operation status Figure 5-5 and the "RUN" light on the LED panel
is illuminated, this is an indication that the grid connection and power generation were successful.
DOCR-071030-A (10/7/2022)
Neutral Line Setting
Yes
No
Figure 5-3 Setting the Neutral Line
Communication Setting
Baud rate:
Address:
Figure 5-4 Communication Setting
E-T:0.0kWh
kWh
60
45
30
15
3
6
9
12
PV1:0.0V
0.0A
Standby Addr:001
9600
0001
E-D:0.0kWh
15
18
21
24h
2015-10-22 12:00:00
Page 71 of 131

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Solectria pvi 50tl-480Solectria pvi 60tl-480

Table of Contents