the loss of AC voltage by way of opening the PV system disconnect switch, inverter circuit breaker or under loss of
grid events, the transmitter stops transmitting the "stay alive" signal sending the MLPE devices into rapid
shutdown. This rapid shutdown system has been UL PVRSS listed and compatibility tested and is a certified
platform to conform to 690.12 of the 2017 National Electric Code. Please refer to the RSD Compatibility and
Listing Matrix Application Note for the most up to date information on models that have been tested and listed
with Solectria inverters.
The wire boxes that have module-level rapid shutdown transmitters integrated into them do not have negative
fusing. This is in conformance with NEC 2017 690.9(C).
Figure 2-4 PVI 50/60TL-480 Inverter Schematic, Module-Level Rapid Shutdown Wire Box
DOCR-071030-A (10/7/2022)
Page 16 of 131