YASKAWA Solectria PVI 25TL-208 Installation And Operation Manual page 79

Commercial 1000vdc string inverters
Table of Contents

Advertisement

Installation and Operation Guide SOLECTRIA® PVI 25TL-208, PVI 50TL-480 and PVI 60TL-480
PARAMETER NAME
GRIDFRQMAX1(HZ)
FRQMAXTRIPT1(S)
GRIDFRQMAX2(HZ)
FRQMAXTRIPT2(S)
GRIDFRQMAX3(HZ)
FRQMAXTRIPT3(S)
GRIDFRQMIN1(HZ)
FRQMINTRIPT1 (S)
GRIDFRQMIN2(HZ)
FRQMINTRIPT2 (S)
GRIDFRQMIN3(HZ)
FRQMINTRIPT3 (S)
DOCR-071030-A (10/7/2022)
DESCRIPTION
Protection
60.00
threshold value
of Level 1 Max.
grid frequency
Trip time of
Level 1 Max. grid
frequency
Protection
60.00
threshold value
of Level 2 Max.
grid frequency
Trip time of
Level 2 Max. grid
frequency
Protection
60.00
threshold value
of Level 3 Max.
grid frequency
Trip time of
Level 3 Max. grid
frequency
Protection
54.00
threshold value
of Level 1 Min.
grid frequency
Trip time of
Level 1 Min. grid
frequency
Protection
54.00
threshold value
of Level 2 Min.
grid frequency
Trip time of
Level 2 Min. grid
frequency
Protection
54.00
threshold value
of Level 3 Min.
grid frequency
Trip time of
Level 3 Min. grid
frequency
MIN
DEFAULT
60.50
0.00
2.00
62.00
0.00
0.16
62.00
0.00
0.16
59.50
0.00
2.00
57.00
0.00
0.16
57.00
0.00
0.16
MAX
MIN
DEFAULT
60.50
65.00
60.00
655.00
0.00
299.50
65.00
60.00
62.00
655.00
0.00
0.16
65.00
60.00
62.00
655.00
0.00
0.16
60.00
54.00
58.50
655.00
0.00
299.50
60.00
54.00
57.00
655.00
0.00
0.16
57.00
60.00
54.00
655.00
0.00
0.16
MAX
65.00
655.00
65.00
655.00
65.00
655.00
60.00
655.00
60.00
655.00
60.00
655.00
Page 79 of 131

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Solectria pvi 50tl-480Solectria pvi 60tl-480