7. Remove the cover of the Wiring Box.
8. Ensure correct polarity of the PV Strings before terminating the DC source circuits within the Wiring Box.
9. Land the input PV circuit conductors by connecting to the DC fuse holders in the Wiring Box.
10. Land the AC conductors from the grid to the AC terminal block in the Wiring Box, ensuring a positive phase
rotation.
11. Land the communication conductors.
12. Seal all the conduit entrances with electrically rated conduit foam to restrict air flow to maintain enclosure's
NEMA Type 4X rating.
13. Replace the plastic shields and the cover of the Wiring Box.

Mechanical Installation

Inverter Environment
The SOLECTRIA PVI 25TL-208, PVI 50TL-480, AND PVI 60TL-480 inverters are equipped with a NEMA Type 4X rated,
Polyester Powder-Coated Aluminum enclosure suitable for outdoor installation in many different climates. Select
the mounting location appropriately taking into consideration snow, wind, rain, direct sun, pests, vegetation
growth, and any other local environmental conditions. To increase its life span, it is recommended that the inverter
be installed out of direct sunlight; for example, under a shade structure, on a north facing building wall, or on north
facing racking. Never install inverters in areas that are prone to flooding, standing water, prolonged snow coverage,
or near explosive or flammable materials.
Explosion or Fire Hazard: Electrical devices can cause fires. Never install in areas prone to explosive gasses,
liquids, or in close proximity to flammable materials.
Maintain NEMA Type 4X Rating: It is the responsibility of the installer to maintain the NEMA Type 4X rating of
the enclosure. Failure to maintain the NEMA Type 4X rating will void the warranty.
Improper Installation Will Void Warranty: Never install the inverter in areas that are prone to flooding, standing
water, or prolonged snow coverage. It is important to ensure the cooling fans and exhausts remain clear from
obstructions at all times.
Temperature Derating: The SOLECTRIA PVI 25TL-208, PVI 50TL-480, and PVI 60TL-480 inverters are rated for a
wide range of operating temperatures. When installed in environments that may experience ambient
DOCR-071030-A (10/7/2022)
WARNING
NOTICE!
NOTICE!
INFO ✔
Page 24 of 131

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Solectria pvi 50tl-480Solectria pvi 60tl-480

Table of Contents