YASKAWA Solectria PVI 25TL-208 Installation And Operation Manual page 87

Commercial 1000vdc string inverters
Table of Contents

Advertisement

Installation and Operation Guide SOLECTRIA® PVI 25TL-208, PVI 50TL-480 and PVI 60TL-480
Table 6-9 Active Power Derating Setup Ranges with Lower Limit, Default, and Upper Limit for IEEE 1547-2018 and CA Rule 21
PARAMETER NAME
VWCURVEV1 (%)
VWCURVEP1 (%)
VWCURVEV2 (%)
VWCURVEP2 (%)
DOCR-071030-A (10/7/2022)
Setting
System Parameters
Control Command
Protection Parameters
LVRT/HVRT Setup
Power Derating Setup
Reactive Power Derating Setup
ARC Parameters
Figure 6-11 Power Derating Parameters
DESCRIPTION
Grid
overvoltage
derating
starting
voltage V1
Grid
overvoltage
derating
starting power
P1
Grid
overvoltage
derating end
voltage V2
Grid
overvoltage
Power vs Grid Voltage
VwCurveV1
VwCurveP1
VwCurveV2
VwCurveP2
OPenLoopRespT(s)
Power vs Grid Frequency
OvrFrqMin(Hz)
OvrFrqMax(Hz)
OvrFrqSlop(P/s)
RecovryFrq(Hz)
OvrFrqRecoveryT(S)
OvrFrqDeratingMode
P1/2
Active Power Derating
CtrMode
Percentage
SETTINGS RANGE
IEEE1547
MIN
DEFAULT
105.00
106.00
0.00
100.00
106.00
110.00
0.0
0.0
106.00%
100.00%
Disable
110.00%
0.0%
10.0%
P1/3
60.40
61.50
0.16%
60.00
60
0
P2/3
0
100.0%
P3/3
RULE 21
MAX
MIN
DEFAULT
109.00
105.00
100.00
0.00
110.00
106.00
100.0
0.0
MAX
106.00
109.00
100.00
100.00
110.00
110.00
0.0
100.0
Page 87 of 131