Siemens SIDOOR AT40 System Manual page 142

Automatic door control units
Hide thumbs Also See for SIDOOR AT40:
Table of Contents

Advertisement

Power supply
7.4 Uninterruptible power supply (UPS)
Recommendations on UPS data
Output voltage
Output frequency
Output power
Wave type
Current voltage distortion
Classification (according to IEC
62040-3)
Example calculation for an M3 motor
Input data
Tag
Value
F
80 N
FR
F
60 N
HC
F
70 N
HO
I
0.1 A
O24
m
180 kg
D
N
5
C
s
0.8 m
D
T
20 s
HC
T
20 s
HO
T
310 s
STBY
v
0.3 m/s
C
A UPS with 600 W and a bridging time of 10 minutes makes approx. 30,000 J available.
140
230V ± 10%
47 ... 53 Hz
> 600 W
Sine
< 5% at full load
VFI
Definition
Door friction without counter‐
weight
Holding time CLOSED
Holding power OPEN
External power supply 24 V
Door weight, total
Cycles OPEN/CLOSED
Door width, 1 leaf in meters
Hold time closed
Hold time open
Standstill time without hold‐
ing power
Closing speed
Calculation
System Manual, 06/2022, A5E42192709-AH
AT40 and ATD400V for elevators