Energy requirements
The entire energy requirements are derived from the following three physical effects:
• Energy requirements of the control unit → W
Quiescent current consumption of the controller over the time to be bridged
• Energy requirements due to holding powers → W
Current consumption due to continuous torques
• Energy requirements due to door movement W
Current consumption during traversing due to system friction and acceleration of the door
leaves
The energy to be stored by the UPS is therefore derived as follows:
The corresponding mathematical equations of these terms are as follows:
Energy requirements of the control unit
Energy requirements of the holding powers
Energy requirements of the door movement
Energy requirements of the UPS ACCU
Definitions of tags
Tag
Unit
F
N
FR
F
N
HC
F
N
HO
I
A
O24
m
kg
D
N
C
s
m
D
T
s
HC
T
s
HO
T
s
STBY
v
m/s
C
v
m/s
O
AT40 and ATD400V for elevators
System Manual, 06/2022, A5E42192709-AH
Definition
Friction force door
Holding power door closed
Holding power door open
Current consumption 24 V external
Door weight
Number of OPEN/CLOSED cycles
Distance door leaves
Holding time CLOSED
Holding time OPEN
Standstill time without holding power
Closing speed
Opening speed
7.4 Uninterruptible power supply (UPS)
AT
HOLD
MOVE
Power supply