EXPERT 2V2SA
Settings:
The static pressure compensation starts
when the static pressure level exceeds the
Hi or Lo static pressure set points.
1. From the main menu, select: INLET.
2. Use the navigation keys to select the fol-
lowing parameters:
Low SP
.00"WC
High SP
.10"WC
Stat. P compens
5%
Compens.delay
30 sec
*These parameters are accessible if the static
pressure compensation feature is enabled in the
User Setup menu.
3. Set the following parameters:
(The parameter adjustment process is explained
in section 3.2 on page 8).
Low SP & High SP — Set the static pres-
sure level below and above which the
static pressure compensation must be
applied on the inlet opening.
Stat. P compens — Select the opening
percentage that must be added or removed
when the static pressure compensation is
applied on the inlet openings. This param-
eter ranges from 0 to 10%. *Note that this
compensation is never applied more than four
times on the inlet opening.
Compens. delay — Each time this delay
has elapsed and the pressure exceeds the
normal range, the static pressure compen-
sation is applied on the inlet opening. This
parameter ranges from 0 to 900 seconds.
EXPERT 2V2SA, rev. 10