Stop T° — Set the temperature over which
the 0-10V fan output is disabled. This pa-
rameter ranges from 0.1°F (0.1°C) above
the start temperature to 120°F (48.9°C).
You can also disable this parameter by
decreasing the value until the word "Off"
is displayed.
Time On and Off — Set the timer be-
ing used by the 0-10V fan output when
the temperature is lower than the start
temperature. The Time On and Off range
from 0 to 900 seconds in increments of
15 seconds.
Probes — The selected 0-10V fan output
operates according to the average tem-
perature a chosen set of probes. Select
what temperature probes are used for
this purpose. Note that the blinking digits
represent the probes that are being used
by the output.