6.1.3. Stage 2 in Min Ventilation

Stage 2 fans can be used to provide minimum
ventilation as shown on the graph below:
Stage 2 Fans
in Minimum Ventilation
Ventilation
Level
Stage 2
full speed
Stage 2
minimum
speed
Stage 2
Off
Stage 1
full speed
0.3°F
Stage 1
minimum
Min.
speed
Vent.
Stage 1
Off
# degrees
to reach full
speed of
stage1
T°SetPoint
- When the room temperature falls below the
start temperature of stage 2, stage 2 fans run
intermittently according to the same timer as
the one used by stage 1.
- When the room temperature increases
above the start temperature of stage 2, stage
2 fans start increasing in speed continuously.
Low Temperature Override: If the room tem-
perature gets too cold while the controller
is in minimum ventilation, low temperature
override functions can be enabled to reduce
the speed of stage 1 fans and to stop stage 2.
This allows reheating the room faster. Refer
to the "User Setup Menu" on page 11
to enable the Low Temperature Override
functions.
0.3°F
Room
# degrees
Temp
to reach full
speed of
stage2
Stage 2
Start T°
1. From the main menu, select: STAGE 2.
2. Use the navigation keys to select this
screen:
Min Ventilation.
On
3. Set the following parameters:
(The parameter adjustment process is explained
in section 3.2 on page 8).
Minimum ventilation — Select "Yes" if to
use stage 2 fans in minimum ventilation.
EXPERT 2V2SA, rev. 10
21