DO NOT SPRAY WATER ON THE CONTROLLER FOR CUSTOMER USE Enter the serial number located on the side of the controller below for future reference. TC5-2V4SA Model number: Serial number: TC5-2V4SA rev.06...
FEATURES The TC5-2V4SA is an electronic device used for environmental control in livestock buildings. It allows the user to maintain a specified target tem- perature by controlling the operation of ventilation and heating equipment. Two stages of variable speed fans can be connected to the controller, as well as two stages of constant-speed fans and two stages of either con- stant-speed fans or heating units.
Page 5
CONTROL OF AIR INLET MOVEMENT If the TC5-2V4SA is used in combination with a PF-5B controller, the move- ment of the air inlets can be coordinated with the operation of the fans using a potentiometer located on the panel drive.
ALL WIRING MUST BE DONE BY AN AUTHORIZED ELECTRI- CIAN AND MUST COMPLY WITH APPLICABLE CODES, LAWS AND REGULATIONS. BE SURE POWER IS OFF BEFORE DO- ING ANY WIRING TO AVOID ELECTRICAL SHOCKS AND EQUIP- WARNING MENT DAMAGE. TC5-2V4SA rev.06...
Return to the Stage 1 bandwidth display by pressing the push-button once again. Selecting A Motor Type for Stage 2 Refer to the list of motors enclosed with this user's manual to determine which type (1 to 10) is appropriate for the motors used. TC5-2V4SA rev.06...
OFF to use Stage 6 for heating and Stage 5 for cooling. ð Set switches # 6 and # 7 to ON to use both stages for heating. Note that if only one stage is used for heating, it must be Stage 6. TC5-2V4SA rev.06...
ON: • Switch # 3 activates the probe connected to input # 2. • Switch # 4 activates the probe connected to input # 3. • Switch # 5 activates the probe connected to input # 4. TC5-2V4SA rev.06...
Page 12
If the probe is defective, the let- ters "PR1" are displayed, alter- nating with the state of the probe TC5-2V4SA rev.06...
Page 13
If the probe is defective, the letters "PR#" are displayed, alternating with the on/off state of the probe and the letter "P". TC5-2V4SA rev.06...
(ii) If, after about 6 seconds, no action is taken by the user, the absolute temperature value is displayed, alternating with "St. 3". In this case, the absolute value is: Set Point + Bandwidth 1 + Offset 2 + Bandwidth 2 + Differential 3. TC5-2V4SA rev.06...
To lock the parameter settings: Set internal switch # 1 to ON. The Locked Parameter Pilot Light turns To unlock the parameter settings: Set internal switch # 1 to OFF. The Locked Parameter Pilot Light turns off. TC5-2V4SA rev.06...
Set the selection knob to ROOM TEMPERATURE / PROBE T . The room temperature is displayed. Viewing Probe Temperatures The controller can display probe temperatures individually. Probes can also be turned on or off to control the temperature in different parts of the building. TC5-2V4SA rev.06...
Page 17
Turn the adjustment knob clockwise a third notch. The room tempera- ture is displayed again. For each individual probe, press the push-button. The temperature read- ing from probe x is displayed, alternating with the letters "Pr x" and the on/off state of the probe. TC5-2V4SA rev.06...
Page 18
Press the push-button to access the other probes, etc. NOTE : If you let the display flash for more than 10 seconds, the control- ler resets the minimum and maximum temperatures currently in memory (the display stops flashing to indicate that the reset has been done). TC5-2V4SA rev.06...
CURVE.The current set point flashes on the display. Use the adjustment knob to adjust the set point to the desired value. NOTE: The temperature set point can be adjusted only if the temperature curve is deactivated (see following section). TC5-2V4SA rev.06...
Certain restrictions apply to reduce the risk of errors: − The highest possible day number is 99. − Decreasing day numbers are not allowed. − Increasing temperatures are not allowed. − The temperature variation cannot exceed 3°F (1.6°C) per day. TC5-2V4SA rev.06...
Page 21
Using the adjustment knob, adjust the set point to the desired value. Once the six points of the curve have been specified, activate the curve as explained below. NOTE : Make sure the temperature curve is deactivated before specify- ing new points (see below). TC5-2V4SA rev.06...
Page 22
OFF appears (thirteen clicks). Turn the adjustment knob clockwise one notch. The word ON flashes on the display and the Temperature Curve Pilot Light flashes, indi- cating that the temperature curve is now activated. Set the selection knob to ROOM TEMPERATURE. TC5-2V4SA rev.06...
Page 23
ON appears (fourteen clicks). Turn the adjustment knob counterclockwise one notch. The word OFF flashes on the display and the Temperature Curve Pilot Light turns off indicating that the temperature curve is now deactivated. Set the selection knob to ROOM TEMPERATURE. TC5-2V4SA rev.06...
VENTILATION SETTINGS OOLING OPERATION The TC5-2V4SA controls two stages of variable-speed fans (Stage 1 - 2), two stages of constant-speed fans (Stage 3 - 4) and two optional stages of constant-speed fans (Stages 5 & 6). TC5-2V4SA rev.06...
Page 25
• At Set Point + Bandwidth 1: Stage 1 fans start decreasing in speed as the temperature decreases. • At Set Point: Stage 1 fans reach minimum speed. • Below the Set Point: stage 1 fans stop operating continuously and operate according to the minimum ventilation cycle at minimum speed. TC5-2V4SA rev.06...
2. To stop the fans, set time on to zero and time off to any value. 3. To run the fans intermittently, set time on to the desired running time and time off to the desired off time. TC5-2V4SA rev.06...
Page 27
Use the adjustment knob to adjust time on to the desired value. Press the push-button. The current time off for Stage 1 flashes on the display, alternating with the letters "Off". Use the adjustment knob to adjust time off to the desired value. TC5-2V4SA rev.06...
This feature also applies when the minimum ventilation speed curve is activated. Note that for the compensation to take place, the compensation feature must be activated by the user. When a compensation is applied to the minimum speed, the compensation pilot light turns on. TC5-2V4SA rev.06...
Page 29
Note that the humidity compensation feature must be activated for this to work. Set the selection knob to STAGE 1 — HUMIDITY CONTROL. The current humidity reading is displayed. TC5-2V4SA rev.06...
Page 30
Set the selection knob to STAGE 1 — HUMIDITY CONTROL. The current humidity reading is displayed. Press the push-button three times. The current on/off state of humidity compensation flashes on the display. Use the adjustment knob to adjust the on/off state to the desired value. TC5-2V4SA rev.06...
When the room temperature rises above the set point, the fans will return to the current minimum speed, calculated according to the minimum speed curve. TC5-2V4SA rev.06...
Page 32
This day number must be greater or equal to the day number specified for the first point of the temperature curve and less than the day number specified for the second point of the temperature curve (see example 1). TC5-2V4SA rev.06...
Page 33
Therefore, if you activate the minimum speed curve today, it will effectively be in operation the moment you activate it. In this case, the current minimum speed will be a value between 10% and 20%. TC5-2V4SA rev.06...
Page 34
The minimum speed curve must be deactivated before specifying the points on the curve (see below). ii) All six points of the curve must be specified. If you do not need six different points, repeat your last minimum speed for each unneces- sary point of the curve. TC5-2V4SA rev.06...
Page 35
Viewing Current Minimum Speed and Day When the minimum speed curve is activated, the current minimum speed and day number can be viewed at any time. To modify the day number, refer to the section on temperature curves. TC5-2V4SA rev.06...
Page 36
ON appears (fourteen clicks). Turn the adjustment knob counterclockwise by one notch. The word OFF flashes on the display. The Minimum Speed Curve Pilot Light starts blinking, indicating that the minimum speed curve is now deac- tivated. TC5-2V4SA rev.06...
11.1°C). Set the selection knob to STAGE 2 — OFFSET/BANDWIDTH. The current offset for Stage 2 flashes on the display, alternating with the letters "OFT". Use the adjustment knob to adjust the offset to the desired value. TC5-2V4SA rev.06...
Page 38
(see the diagram above). The differentials can be adjusted between 0.5°F and 20.0°F (0.3°C and 11.1°C). Set the selection knob to COOLING — DIFFERENTIALS 3-6. The current differential for Stage 3 is displayed, alternating with the letters «St. 3». TC5-2V4SA rev.06...
Stage 2 minimum speed during a user-defined de- icing time. Then, the Stage 2 fans are turned off and operation of Stage 1 fans is resumed at the appropriate speed. To deactivate de-icing, set de-icing time to zero. TC5-2V4SA rev.06...
Page 40
Set the selection knob to STAGE 2 — MIN. SPEED. The current minimum speed for Stage 2 flashes on the display. Press the push-button twice. The current de-icing time is displayed, alternating with the letters "On". Use the adjustment knob to adjust the de-icing time to the desired value. TC5-2V4SA rev.06...
The mist units operate according to a timer cycle. Time on is the running time of the mist units and time off is the off time of the mist units. TIME ON TIME OFF TC5-2V4SA rev.06...
Page 42
The current time on for the mist cycle is displayed, alternating with the letters "On". Press the push-button twice. The mist offset is displayed, alternating with the letters "Oft". Using the adjustment knob, set the offset to the desired value. TC5-2V4SA rev.06...
Page 43
The current time on for the mist cycle is displayed, alternating with the letters "On". Press the push-button four times. The current turn off level flashes on the display. Use the adjustment knob to set the turn off level to the desired value. TC5-2V4SA rev.06...
If the room temperature falls: - at Set Point - Heater 1 Offset - Heater 1 Diff.: Heater 1 turns on. - at Set Point - Heater 1 Offset - Heater 1 Diff. - Heater 2 Diff.: Heater 2 turns on. TC5-2V4SA rev.06...
Page 45
1 may be insufficient. A built-in protection will oper- ate the fans according to the probes of the zone with the highest tempera- ture whenever the temperature difference between zones is greater than a user-defined value. TC5-2V4SA rev.06...
Page 46
If the room temperature falls: - at Set Point - Heater Offset 1 - Diff. 1 (Probe 1) : Heater 1 turns on. - at Set Point - Heater Offset 2 - Diff. 2 (Probe 2) : Heater 2 turns on. TC5-2V4SA rev.06...
Page 47
OFF./DIFF. The current heater offset is displayed, alternating with the letters "OFT". Press the push-button. The heater differential is displayed, alternat- ing with the letters "DIF". Use the adjustment knob to adjust the differential to the desired value. TC5-2V4SA rev.06...
Page 48
"OFT". Press the push-button twice. The maximum temperature difference between zones is displayed, alternating with the letters "dif Zon". Use the adjustment knob to adjust the temperature difference to the desired value. TC5-2V4SA rev.06...
Press the push-button. The current high alarm offset flashes on the display, alternating with the word "HI". Use the adjustment knob to set the high alarm offset to the desired value. TC5-2V4SA rev.06...
Turn the selector knob to the ROOM TEMPERATURE position. The current room temperature is displayed. Press and hold the push-button for 3 seconds. NOTE: If no user activity is recorded after 4 minutes in test mode, the controller resumes normal operation. TC5-2V4SA rev.06...
There is electrical noise Do not run probe cables next to near an extended probe other power cables. When cable. crossing other power cables, cross at 90 TC5-2V4SA rev.06...
Page 52
Adjust the minimum speed to a The minimum speed is higher value. too low. The fan motor is Check if motor is defective by defective. connecting it to an alternate power supply. Replace the motor if it still doesn't operate. TC5-2V4SA rev.06...
Page 53
(N for 115V or L2 for 230V) to activate the motor. Also, be sure the stage 1 COMMON is supplied by line L1. Humidity compensation Adjust set point or deactivate is activated and relative compensation as required. humidity exceeds set point. TC5-2V4SA rev.06...
Page 54
If it still is not operating. Listen to see if there is a clicking The controller is sound when the Stage's pilot light defective. turns on. If there is no clicking sound, contact your distributor to repair the controller. TC5-2V4SA rev.06...
De- i ci ng Ti me 0 seconds i ncrement s of 1 second Stages 0.5 to 20 Di f f erenti al F( 1 . 1 3 t o 6 ( 0 . 3 t o 11. 1 TC5-2V4SA rev.06...
Page 57
These initial parameter settings will not be retained in the controller's memory. Each new setting will replace the preceding one. ii) If the power supply is cut off, the last parameter settings will be re- tained in memory until the power is restored. TC5-2V4SA rev.06...
OFFSET: An offset is a temperature difference from the set point that normally defines a cut-off point for a stage operation. For example, a heater offset of 2°F means the heaters will turn off at 2°F below the set point. TC5-2V4SA rev.06...
Page 59
ZONED HEATERS: When zoned heaters are used, heaters in each zone operate according to their own probes rather than the average temperature for the entire room. In this way, heaters across zones are independent of one another. TC5-2V4SA rev.06...