Figure 58. BACnet device ID
BACnet networks without a Tracer
controller
On BACnet networks without a Tracer
controller, the Device ID can be assigned one of two ways:
•
It can be the same number as the MAC Address,
determined by the rotary address dials on the UC400-B
controller. For example, if the rotary address dials are
set to 042, both the MAC Address and the BACnet
Device ID are 042.
•
It can be soft set using the Tracer
the BACnet Device ID is set using the Tracer
Figure 59. Example of BACnet link wiring with multiple UC400-B controllers
+
Trane
BACnet
Terminator
Tracer SC
Power Supply
Read all of the warnings, cautions, and notices below
before proceeding with this section.
BCX-SVX002A-EN
®
SC system
®
SC system
®
TU service tool. If
®
TU
1 2 3 4
4
3
2
1
1 2 3 4
4
3
2
1
4
3
2
1
24VDC
Gnd
24VDC
Gnd
BACnet
BACnet
1 2 3 4
1 2 3 4
IMC
IMC
UC400-B
UC400-B
Zone Sensor
Zone Sensor
service tool, the rotary address dials only affect the
MAC Address, they do not affect the BACnet Device ID.
BACnet networks with a Tracer
On BACnet networks with a Tracer
the Device ID for the UC400-B controller is always soft set
by the system controller using the following scheme
illustrated below.
Note: The BACnet Device ID is displayed as the Software
Device ID on the Tracer
page in the Protocol group.
1 2 3 4
2
4
3
2
1
4
3
1
4
3
2
1
24VDC
Gnd
BACnet
1 2 3 4
IMC
+
UC400-B
Zone Sensor
Installation - Controls
®
SC system controller
®
SC system controller,
®
TU Controller Settings
67