Table 54. Diagnostics generated by UC400-B controller (continued)
Diagnostic
Probable Cause
Generic AIP failure
Invalid or missing value
for generic analog input.
Local fan mode
Invalid or missing fan-
failure
speed switch (reverts to
default fan speed).
Local setpoint failure
Invalid or missing value
for zone temperature
setpoint (reverts to default
setpoint).
(a)
For detailed information about zone temperature control methods, refer to

Fans with UC400-B Controller

Table 55. Fan does not energize
Probable Cause
Explanation
Unit wiring
The wiring between the controller outputs and the fan relays and contacts must be present and correct for normal fan
operation. Refer to applicable wiring diagram.
Failed end device
The fan motor and relay must be checked to ensure proper operation.
Normal operation
The fan will turn OFF when:
If the controller is in unoccupied mode, the fan cycles between OFF and the highest fan speed.
No power to the controller
If the controller does not have power, the unit fan does not operate. For the controller to operate normally, it must have an
input voltage of 24 Vac. If the Marquee/Power LED is OFF continuously, the controller does not have sufficient power or
has failed.
Diagnostic present
Several diagnostics affect fan operation. For detailed information about these diagnostics, refer to
Unit configuration
The controller must be properly configured based on the actual installed end devices and application. If the unit
configuration does not match the actual end device, the fans may not work correctly.
Random start observed
After power-up, the controller always observes a random start from 5 to 30 seconds. The controller remains OFF until the
random start time expires.
Cycling fan operation/
The controller continuously operates the fan when in the occupied, occupied standby, or occupied bypass mode. When
continuous
the controller is in the unoccupied mode, the fan is cycled between high speed and OFF with capacity.
Unoccupied operation
Even if the controller is configured for continuous fan operation, the fan normally cycles with capacity during unoccupied
mode. While unoccupied, the fan cycles ON or OFF with heating/cooling to provide varying amounts of heating or cooling
to the space.
Fan mode off
If a local fan mode switch determines the fan operation, the OFF position controls the fan to off.
Requested mode off
The user can communicate a desired operating mode (such as OFF, heat, and cool) to the controller. If OFF is
communicated to the controller, the unit controls the fan to off. There is no heating or cooling.
BCX-SVX002A-EN
Consequences
Fan Unaffected
Valves Unaffected
Outdoor air damper Unaffected
DX cooling/electric heat Unaffected
Fan Unaffected
Valves Unaffected
Outdoor air damper Unaffected
DX cooling/electric heat Unaffected
Fan Unaffected
Valves Unaffected
Outdoor air damper Unaffected
DX cooling/electric heat Unaffected
Zone Temperature Control, p.
The controller receives a communicated off signal.
The fan-speed switch is set to OFF if no communicated value is present.
Specific diagnostics are generated.
The default fan speed is set to OFF and the fan is operating in the Auto mode.
Diagnostics and Troubleshooting
Diagnostic Type
Informational
Automatic
Automatic
108.
Table 54, p.
134.
135