Sensor Diagnostics; Testing Signal Strength - Trane BCHE Installation, Operation And Maintenance Manual

Blower coil air handler
Table of Contents

Advertisement

Diagnostics and Troubleshooting
Table 44. Diagnostics on the receiver
LED state
LED1: Off
LED2: Off
LED3: 1-blink pattern repeated
continuously
(a)
LED1: Off
LED2: Off
LED3: 2-blink pattern repeated
continuously
(a)
LED1: Off
LED2: Off
LED3: 3-blink pattern repeated
continuously
(a)
(a)
Blink pattern is On for 1/4 s, Off for 1/4 s, with 2 s Off between repetitions.

Sensor Diagnostics

LED1, LED2, and LED3, located on the WZS respond to
diagnostics by exhibiting specific blinking patterns. View
their response by pressing the Test button.
Table 45. Diagnostics for wireless zone sensors and error code shown on wireless display sensor
LED state when Test button is pressed on
WZS
n/a
LED1: Off
LED2: Off
LED3
(a)
: 1-blink pattern repeated 3 times
LED1: Off
LED2: Off
(a)
LED3
: 2-blink pattern repeated 3 times
LED1: Off
LED2: Off
LED3
(a)
: 3-blink pattern repeated 3 times
LED1: Off
LED2: Off
LED3
(a)
: 4-blink pattern repeated 3 times
(a)
Blink pattern is On for 1/4 s, Off for 1/4 s, with 2 s Off between repetitions.

Testing Signal Strength

To initiate a signal strength test, push the Test button on the
sensor (see location of Test button in
and
Figure 104, p.
125.
Models WZS: LED1, LED2, and LED3 respond by
indicating signal strength. You can view them on the sensor
(Table 46, p.
127) and the receiver
126
Indicates...
Disassociated
Receiver is not associated, waiting for a sensor.
Receiver lost communication with sensor.
Receiver has no devices on its wireless personal area network.
Association with a device has been manually removed.
Address set to 000
Address not set to between 001–999.
Not configured
Receiver configuration properties not properly set (defective receiver).
Error code shown on WDS
E0, E5, E7
E1
E2
E3
E4
Figure 103, p. 125
(Table 47, p.
127).
Error codes appear on the WDS when diagnostics occur
(see the following table).
Indicates...
Sensor failure
Replace sensor
Disassociated
Sensor is not associated with a receiver.
Address set to 000
Address not set to between 001–999.
Software error
Replace sensor
Input voltage too high
No RF transmission is permitted with an input battery voltage
greater than 3.9 V.
Model WDS: Test symbols on the sensor display indicate
signal strength
(Table 46, p.
on the receiver, respond by indicating signal strength
(Table 47, p.
127).
127). LED1, LED2, and LED3,
BCX-SVX002A-EN