Trane BCHE Installation, Operation And Maintenance Manual page 66

Blower coil air handler
Table of Contents

Advertisement

Installation - Controls
Figure 57. Setting rotary address dials
1
2
3
4
5
6
14 13 12 11 10 9 8 7 6 5 4
J16
Phoenix
MAC Address
The MAC Address is required by the RS-485
communication protocol on which BACnet operates. A
UC400-B controller can use a MAC Address from 001 to
120.
Important: Each device on the link must have a unique
MAC Address/Device ID. The controller rotary
addresses should be sequentially set, with no
gaps in the numbering, starting with 001 on
each link (for example 001, 002, 003, 004 and
so on). A duplicate address or a 000 address
setting will interrupt communications and
cause the Tracer
process to fail.
66
Address
0
0
0
1 2 3
5
5
5
J14 - JST
3 2 1
J17
14 Pin AMP
Low Coil
Entering
Detection
Water
(NC)
Temp
Condensate
Overflow (NC)
®
SC device installation
Comm In
Comm Out
Zone Sensor
Comm -
Serv Tool
Connection
Comm +
GND
24VDC
Auxiliary 24 Vdc
Output
1
2
3
4
J18
Phoenix
BACnet Device ID
The BACnet Device ID is required by the BACnet network.
Each device must have a unique number from 001 to
4094302. See the following figure.
BCX-SVX002A-EN