Power Wiring - Trane 2TEE3F31A1000A Installer's Manual

Convertible variable speed - air handlers 2-1/2 - 5 ton
Hide thumbs Also See for 2TEE3F31A1000A:
Table of Contents

Advertisement

Manufactured
traps
EZT- 105
2" MINIMUM
_2" MINIMUM
Figure 15
Field fabricated trap
i
I
i
i
I
i
Close as possible
_ _
I [II
]
Trap must be within 4'
of air handler condensate
drain connection
Figure 16
4. Do not use reducing
fittings in the condensate
drain
lines.
5. Slope the drain
lines downward
a minimum
of 1/4"
per foot.
6. Insulate
the
primary
drain
to prevent
sweating
where
pipe temperature
could meet
or fall below
dewpoint
temperatures.
7. Provide
means
for drainage
to prevent
winter
freeze-up
of condensate
line.
8. Do not connect the drain
line to a closed drain sys-
tem.
9. Use Teflon _ tape on the air handler
drain line con-
nections!
Do Not Use pipe joint compound
or PVC/
CPVC cement!
It is always recommended
that
an auxiliary
drain pan
be installed
under a horizontally
installed
air handler.
Connect the auxiliary
drain line to a separate
drain line
(no trap is needed in this line) and terminate
according
to local codes.
NOTE: DO NOT use a torch or flame near the plastic
drain pan coupling.
Installer's
Guide
NOTE: DO NOT tighten the drain pipe excessively. Sup-
port the condensate piping and traps outside the unit
to prevent strain on the drain coupfing.
H. ELECTRICAL
i
POWER WIRING
1. These Air Handlers
are shipped
from the factory
wired for 230 volts. The units may be wired for 208
volts. Follow instructions
on unit wiring diagram
lo-
cated on blower housing
and in the Service
Facts
document
included with the unit.
2. The selection of wire and fuse sizes should be made
according
to the Minimum
Branch Circuit Ampacity
and the Maximum
Overcurrent
Device listed on the
unit nameplate.
TO PREVENT INJURY OR DEATH DUE TO ELECTRICAL
SHOCK OR CONTACT WITH MOVING PARTS, LOCK
UNIT DISCONNECT SWITCH IN OPEN POSITION BE-
FORE SERVICING UNIT.
3. Field wiring
diagrams
for electric
heaters
and unit
accessories
are shipped with the accessory.
4. Wiring must conform to National
and Local codes.
If an electric
heater
is not installed,
the Knockout
Plate pro-
vided in the Accessory
Kit MUST be installed
on the air han-
dler and the conduit
terminated
to it.
The electrical
connec-
tions are made
using
the two power leads
and ground
wire
connections
which
are located
near
the
discharge
of the
blower.
NOTE: If air handler is used with or without a heater,
the electrical entry hole as well as any other cabinet
penetrations
must be sealed air-tight.
18-GE04D2-10
9