Trane BCHE Installation, Operation And Maintenance Manual page 105

Blower coil air handler
Table of Contents

Advertisement

Table 34. Zone sensor thermistor curve (Resistance in Ohms) (continued)
°C
°F
R
11
51.8
19028
12
53.6
18139
13
55.4
17297
14
57.2
16499
15
59
15743
16
60.8
15025
17
62.6
14345
18
64.4
13700
19
66.2
13087
20
68
12505
21
69.8
11953
22
71.6
11428
23
73.4
10929
24
75.2
10455
Space Temperature Measurement
Trane zone sensors use a 10kΩ thermistor to measure the
space temperature. Typically, zone sensors are wall-
mounted in the room and include a space temperature
thermistor. As an option, the zone sensor can be unit-
mounted with a separate space temperature thermistor
located in the unit's return air stream. If both a hard-wired
and communicated space temperature value exist, the
controller ignores the hard-wired space temperature input
and uses the communicated value.
External Setpoint Adjustment
Zone sensors with an external setpoint adjustment (1kΩ)
provide the controller with a local setpoint (50°F to 85°F or
10°C to 29.4°C). The external setpoint is exposed on the
zone sensor's front cover.
When the hard-wired setpoint adjustment is used to
determine the setpoints, all unit setpoints are calculated
based on the hard-wired setpoint value, the configured
setpoints, and the active mode of the controller. The hard-
wired setpoint is used with the controller's occupancy mode
(occupied, occupied standby, or unoccupied), the heating
or cooling mode, the temperature deadband values, and
the heating and cooling setpoints (high and low limits) to
determine the controller's active setpoint.
When a building automation system or other controller
communicates a setpoint to the controller, the controller
ignores the hard-wired setpoint input and uses the
communicated value. The exception is the unoccupied
mode, when the controller always uses the stored default
unoccupied setpoints. After the controller completes all
setpoint calculations, based on the requested setpoint, the
occupancy mode, the heating and cooling mode, and other
factors, the calculated setpoint is validated against the
following setpoint limits:
BCX-SVX002A-EN
°C
°F
R
36
96.8
6248
37
98.6
6006
38
100.4
5777
39
102.2
5559
40
104
5352
41
105.8
5156
42
107.6
4969
43
109.4
4791
44
111.2
4621
45
113
4460
46
114.8
4306
47
116.6
4160
48
118.4
4020
49
120.2
3886
°C
°F
R
61
141.8
2397
62
143.6
2309
63
145.4
2225
64
147.2
2145
65
149
2070
66
150.8
1998
67
152.6
1929
68
154.4
1864
69
156.2
1802
70
158
1742
71
159.8
1686
72
161.6
1632
73
163.4
1580
74
165.2
1531
Heating setpoint high limit
Heating setpoint low limit
Cooling setpoint high limit
Cooling setpoint low limit
These setpoint limits only apply to the occupied and
occupied standby heating and cooling setpoints. These
setpoint limits do not apply to the unoccupied heating and
cooling setpoints stored in the controller's configuration.
When the controller is in unoccupied mode, it always uses
the stored unoccupied heating and cooling setpoints.The
unit can also be configured to enable or disable the local
(hard-wired) setpoint. This parameter provides additional
flexibility to allow you to apply communicated, hard-wired,
or default setpoints without making physical changes to the
unit.
Similar to hard-wired setpoints, the effective setpoint value
for a communicated setpoint is determined based on the
stored default setpoints (which determines the occupied
and occupied standby temperature deadbands) and the
controller's occupancy mode.
Fan Switch
The zone sensor fan switch provides the controller with an
occupied (and occupied standby) fan request signal (Off,
Low, Medium, High, Auto). If the fan control request is
communicated to the controller, the controller ignores the
hard-wired fan switch input and uses the communicated
value. The zone sensor fan switch input can be enabled or
disabled through configuration using the Rover service
tool. If the zone sensor switch is disabled, the controller
resorts to its stored configuration default fan speeds for
heating and cooling, unless the controller receives a
communicated fan input.
Start-Up
°C
°F
R
86
186.8
1041
87
188.6
1009
88
190.4
978
89
192.2
948
90
194
920
91
195.8
892
92
197.6
865
93
199.4
839
94
201.2
814
95
203
790
96
204.8
767
97
206.6
744
98
208.4
722
99
210.2
701
105