Digit 28 — Coil #1 Control Valve Cv
0 = None
A = 2-way 2.3 Cv 3/4-in. valve
B = 2-way 3.3 Cv 3/4-in. valve
C = 2-way 4.6 Cv 3/4-in. valve
D = 2-way and 3-way 7.4 Cv 1-in. valve
E = 2-way and 3-way 10.0 Cv 1-in. valve
F = 3-way 1.0 Cv 1/2-in. valve
G = 3-Way 2.7 Cv 1/2-in. valve
H = 3-Way 4.6 Cv 3/4-in. valve
J= 2-way PIC 0.9 GPM
K = 2-way PIC 2 GPM
L = 2-way PIC 4.3 GPM
M = 2-way PIC 9 GPM
Digit 29 — Coil #1 Piping Package
0 = Factory set
Digit 30 — Coil #2 Control Valve
0 = None
A = 2-way, 2 position N.C.
B = 2-way, 2 position N.O.
C = 3-way, 2 position N.C.
D = 3-way, 2 position N.O.
E = 2-way, modulating
F = 3-way, modulating
G = Field supplied, 2 position N.C.
H = Field supplied, 2 position N.O.
J = Field supplied, modulating
K = Field supplied, analog (2-10 VDC)
Digit 31 — Coil #2 Control Valve Cv
0 = None
A = 2-way 2.3 Cv 3/4-in. valve
B = 2-way 3.3 Cv 3/4-in. valve
C = 2-way 4.6 Cv 3/4-in. valve
D = 2-way and 3-way 7.4 Cv 1-in.
E = 2-way and 3-way 10.0 Cv 1-in. valve
F = 3-way 1.0 Cv 1/2-in.valve
G = 3-way 2.7 Cv 1/2-in. valve
H = 3-way 4.6 Cv 3/4-in. valve
J = 2-way PIC 0.9 GPM
K = 2-way PIC 2 GPM
L = 2-way PIC 4.3 GPM
M = 2-way PIC 9 GPM
Digit 32 — Coil #2 Piping Package
0 = Future offering
Digit 33 — Remote Heat Options
0 = Future offering
Digit 34 — Mixing Box Damper Actuator
0 = None
2 = Modulating, N.C.
2 = Modulating, N.O.
BCX-SVX002A-EN
Digit 35 — Factory Mounted Control
Options
0 = None
A = Condensate overflow
B = Condensate Overflow and Low Limit
Digit 36 — Control Options 2
0 = None
A = Outside air sensor, field mounted
B = Discharge air sensor
C = Outside air and discharge air sensor
Digit 37 — Control Options 3
0 = None
A = Dehumidification with local sensor
B = CO
sensor
2
®
C = Air-Fi
Dehumidification and CO
®
D = Air-Fi
Dehumidification
®
E = Air-Fi
CO
2
Digit 38 — Zone Sensors
0 = None
A = Wall-mounted temperature sensor (OCC/
UNOCC, COMM)
B = Wall-mounted
C = Wall-mounted temperature sensor (SP,
OALMH, OCC/UNOCC, COMM)
D = Wall-mounted display sensor (SP, OALHH,
COMM)
E = Wireless display sensor, Unit-mounted
receiver (SP, OALMH)
F = Wall-mounted FSS
Digit 39 — Seismic Certification
0 = None
A = IBC seismic certification
B = OSHPD seismic certification
Digit 40 — Extra filter
0 = None
1 = Extra 1-in. throwaway ship loose
2 = Extra 2-in. MERV 8 pleated throwaway ship
loose
3 = Extra 2-in. MERV 13 pleated throwaway ship
loose
4 = Extra 2-in. MERV 8 and MERV 13 pleated
throwaway ship loose