Ac Power Consumption For The San768C-6 Director; Dissipation For 3000 W Ac Power Supplies For Different Solutions With 32-G Fibre Channel Ports; Consumption For San768C-6 Director - IBM SAN192C-6 Installation, Service And User Manual

Hide thumbs Also See for SAN192C-6:
Table of Contents

Advertisement

Table 27. Requirements for 3000 W AC Power Supplies  (continued)
Module Type/ Product
Number
SAN768C-6 Fan Module
SAN384C-6 Crossbar
Switching Fabric1 Module
SAN192C-6 Fan Module
Table 28. Dissipation for 3000 W AC Power Supplies for Different Solutions with 32-G Fibre Channel ports using
IBM c-type SAN 48 port 32Gbps Switching Module and six Fabric Modules.
Number of
Switching Modules
Number of Ports
1
48
2
96
3
144
4
192
5
240
6
288
7
336
8
384

AC Power Consumption for the SAN768C-6 Director

Table 29 on page 141 shows the typical AC power consumption for the SAN768C-6 Director.
Table 29. Consumption for SAN768C-6 Director
Speed/Module
Number of
Type
Fabric Modules
32-G Fibre
6
Channel ports
with SAN c-type
48-port 32-
Gbps Switching
Module
Quantity
3
Power Required (watts)
Typical
1440
1700
1960
2220
2480
2740
3000
3260
Typical AC Power Consumption (Watts)
192 ports
2545
Power Required (watts)
Maximum
900
600
300
Total Worst Case
3430
3780
4130
4480
4830
5180
5530
5880
288 ports
384 ports
3065
3585
Appendix A. Product Specifications  141
Typical
75
50
40
Heat Dissipation
(BTU/hr)
12861
14173
15486
16798
18111
19423
20735
22048
768 ports
5665

Advertisement