Default Operations - Trane ReliaTel Diagnostic Manual

Microprocessor controls
Hide thumbs Also See for ReliaTel:
Table of Contents

Advertisement

ReliaTel Refrigeration Module (RTRM)
LonTalk Communication Interface (LCI)
1. When an LCI (Lontalk Communication Interface) is installed on a Voyager Commercial VAV unit,
2. The MWU terminate setpoint is identified as NCI (Network Configuration Input)
3. The MWU initiate setpoint is nciSetpoints.occupied heat - 1.5F .

Default Operations

The ReliaTel Refrigeration Module (RTRM) can accept input from any of the following:
Mechanical Zone Sensor Module (ZSM) BAYSENS106-111A, AYSTAT106A-109A.
Programmable Zone Sensor BAYSENS119*, AYSTAT666*Conventional thermostat BAYSTAT036-
038A (or similar).
ICS systems – Tracer, Tracker, VariTrac With each installed device, default modes of operation come
into play, depending on that device's inputs. Following is a summary of functions and defaults.
Table 2.
Default operation for Mechanical ZSM (CV Only):
J6 Input/connection
J6-1- Zone Temperature
J6-2 Common terminal for 1-5
J6-3 Cooling Set Point (CSP)
J6-5*- Heating Set Point (HSP)
J6-3&5- No CSP or HSP from ZSM
J6-4- Mode Input from ZSM
J6-6*- Common terminal for 7-10
J6-7*- Heat indication
J6-8*-Cool indication
J6-9*- System indication
J6-10*- Service indication
*these connections are only on certain model ZSM's
Table 3.
Default operation for Programmable ZSM:
J6 Input/connection
J6-7- Heat indication from RTRM to ZSM
J6-8- Cool indication from RTRM to ZSM
J6-9- System indication from RTRM to ZSM
J6-10- Service indication from RTRM to ZSM
J6-11- Common
J6-12- Communication
J6-14-24 VAC power
*cool fail indication can occur for several reasons. See diagnostic section for more on this.
34
the morning Warmup (MWU) setpoint located on the RTAM board is ignored. The Morning
Warmup and Daytime Warmup setpoints come from the higher priority LCI-R DAC.
nciSetpoints.occupied heat. The default setpoint is 71F .
if no input/connection this happens:
Unit stops
Unit stops
HSP + 3F if Local Unit Mode is Auto, otherwise Local HSP
Local CSP - 3F if Local Unit Mode is Auto, otherwise, Local CSP
74F CSP, 71F HSP
Auto Changeover with continuous fan
LED's will not function any time
LED will not come on while heating
LED will not flash during heat fail
LED will not come on while cooling
LED will not flash during cool fail*
LED will not come on while unit has power
LED will not come on when CFS or FFS trips
if no input/connection this happens:
"Heat" will not be displayed while heating
"Heat fail" will not be displayed during heat fail
"Cool" will not be displayed while cooling
"Cool fail" will not be displayed during cool fail*
Colon (:) will not blink during normal operation
"Test" will not be displayed during TEST mode
"Service" will not be displayed when clogged filter switch has tripped
"Service" will not flash when the FFS has tripped
No display, no communication
No communication- "Cool fail" indication
No display, no communication
RT-SVD03G-EN