Trane ReliaTel Diagnostic Manual page 40

Microprocessor controls
Hide thumbs Also See for ReliaTel:
Table of Contents

Advertisement

ReliaTel Option Module (RTOM)
Table 8.
Table 9.
40
RTOM Supply Air Reheat Setpoint
Voltage (Vdc)
Setpoint (ºF)
0.002
65
0.169
65.5
0.317
66
0.395
66.5
0.552
67
0.672
67.5
0.785
68
0.915
68.5
1.028
69
1.114
69.5
1.206
70
1.275
70.5
1.365
71
1.445
71.5
1.525
72
1.610
72.5
RTOM Dehumidification Setpoint
Voltage (Vdc)
Setpoint (%)
0.002
40
0.238
41
0.445
42
0.539
43
0.677
44
0.811
45
0.984
46
1.117
47
1.245
48
1.349
49
1.428
50
1.552
51
1.625
52
Voltage (Vdc)
Setpoint (ºF)
1.683
1.766
73.5
1.822
1.887
74.5
1.940
1.998
75.5
2.064
2.118
76.5
2.175
2.196
77.5
2.234
2.275
78.5
2.318
2.368
79.5
2.415
Voltage (Vdc)
Setpoint (%)
1.745
1.824
1.853
1.929
1.978
2.07
2.136
2.184
2.259
2.268
2.324
2.397
2.448
73
74
75
76
77
78
79
80
53
54
55
56
57
58
59
60
61
62
63
64
65
RT-SVD03G-EN