Trane ReliaTel Diagnostic Manual page 16

Microprocessor controls
Hide thumbs Also See for ReliaTel:
Table of Contents

Advertisement

Module Flow Diagram
RTEM
Figure 6. Economizer Module (RTEM)
DCV Mode
Refrigeration
Module
24 VAC
16
ReliaTel Economizer Module
ModBus Communication
24 VAC
DCV Min Pos 0-40/50%
Design Min Pos 0-10/50%
C
B
A
D
E
DCV Setpoint LL
300-1900 ppm
(RTRM v8.0 & later)
DCV Setpoint UL
500-1500 ppm (pre-RTRM
v8.0)
1000-2000 ppm (RTRM
v8.0 & later)
MA Sensor
Mixed Air Temp (AIP)
10K 25C Neg Coeff
RH Sensor
Return Air Relative Humidity (AIP)
4-20 mA Pos Coeff
RA Sensor
Return Air Temp (AIP)
10K 25C Neg Coeff
Outdoor Air Relative Humidity (AIP)
RH Sensor
4-20 mA Pos Coeff
C0 2 Sensor
IAQ Sensor (C0 2 ) (AIP)
0-10 VDC
Potentiometer
Remote Minimum Position Pot. (AIP)
0-270 Ohm
Power Exhaust
Status LED
Enthalpy/Temperature
Setpoint Pot.
PWR
EXH
relay
24 VAC
RT-SVD03G-EN