Thermostats and Sensors
BAYSENS106*/ASYSTAT106*
Accessory Heat / Cool Zone Sensor Module (ZSM) single set point, manual changeover. Four
conductors required.
Figure 37. BAYSENS106A/ASYSTAT106A
BAYSENS107A/ASYSTAT107A
Accessory Heat Pump Zone Sensor Module (ZSM) single set point, manual changeover. Six
conductors required.
Figure 38. BAYSENS107A/ASYSTAT107A
64
Part Number – SEN01515
Part Number – SEN01528
RT1 thermistor,
10 k at 25°C
Note 1:
Temperature
Calibration
Pot 1 is
setpoint
Pot 1 (see
factory
Pot 5,
calibrated.
1 k
Field
adjustment
voids
warranty.
System
SW1
Fan
Auto
SW2
On
RT1 thermistor,
10 k at 25°C
Note 1:
Temperature
Calibration
Pot 1 is
setpoint
Pot 1 (see
factory
Pot 5,
calibrated.
1 k
Field
adjustment
voids
warranty.
System
SW1
Fan
Auto
SW2
On
R6, 8.45 k
Zone
R11, zero
temperature
Signal common
Cool setpoint (CSP)
Note 1
)
Mode
(Sys/Fan switch)
TB1
R1, 4.87 k
Cool
R2, 2.32 k
Off
R3, 19.6 k
Heat
R6, 8.45 k
Zone
R9, zero
temperature
Signal common
Cool setpoint (CSP)
Note 1
)
Mode
(Sys/Fan switch)
R1, 4.87 k
Cool
TB1
R2, 2.32 k
Off
R3, 19.6 k
Heat
R4, 34.8 k
EM Heat
LED Common
6
CR3
LED Heat
7
Green
TB2
RT-SVD03G-EN
1
2
3
4
1
2
3
4