Figure 72. Voyager Commercial Modulating Hot Gas Reheat
C
O
N
D
+
S
B
C
L
RT-SVD03G-EN
Modulating Dehumidification with Hot Gas Reheat (27.5-50 Tons)
C
O
M
P
Time Delayed
R
E
LPC
S
S
O
R
Modulating
Valves
RH
Check
Valve
RTRM handles the main dehumidification logic.
RTOM contains the humidity and supply air set point.
RTDM (New module) handles the reheat/cooling valve and pump out relay control.
Customer adjustable set points
• Supply air reheat set point located on RTOM (65-80ºF default 70ºF)
• Dehumidification (humidity) set point located on RTOM (40-65% default 50%)
• VAV Dehumidification Override Zone Cooling and Heating Set points (75ºF Cooling, 68ºF
Heating). A customer can adjust them if a CV Remote Zone sensor is connected to the RTRM
or by using resistors.
S
S
0.1" Bleed
line
R
E
H
E
A
T
TXV bulb
E
V
A
P
O
R
A
T
O
R
129