Trane ReliaTel Diagnostic Manual page 156

Microprocessor controls
Hide thumbs Also See for ReliaTel:
Table of Contents

Advertisement

Voyager Commercial 27½ to 50 Tons CV and VAV
Table 50. VAV Setpoints
Resistance
DC Volts
(Ohms)
380
1.38
390
1.40
400
1.43
410
1.45
420
1.48
430
1.50
440
1.53
450
1.55
460
1.58
470
1.60
480
1.62
490
1.64
500
1.67
510
1.69
520
1.71
530
1.73
540
1.75
550
1.77
560
1.79
570
1.82
580
1.84
590
1.86
600
1.88
610
1.89
620
1.91
630
1.93
640
1.95
650
1.97
660
1.99
670
2.01
680
2.02
690
2.04
700
2.06
710
2.08
720
2.09
730
2.11
740
2.13
750
2.14
760
2.16
156
Supply
1.
Air
Supply Air
Supply Air
Pressure
Cooling
Reset
Setpoint
Setpoint
Amount
J7-1,2
J7-3,4
J7-5,6
"WC
Deg F
Deg F
1.06
56.89
8.45
1.09
57.38
8.69
1.11
57.78
8.89
1.14
58.18
9.09
1.16
58.59
9.29
1.19
58.99
9.49
1.21
59.39
9.70
1.24
59.80
9.90
1.26
60.20
10.10
1.29
60.60
10.30
1.31
61.00
10.50
1.33
61.33
10.66
1.36
61.73
10.86
1.39
62.25
11.12
1.43
62.81
11.41
1.45
63.26
11.63
1.49
63.83
11.91
1.52
64.28
12.14
1.55
64.73
12.36
1.57
65.18
12.59
1.60
65.63
12.82
1.63
66.08
13.04
1.67
66.65
13.32
1.69
66.99
13.49
1.71
67.44
13.72
1.74
67.89
13.94
1.77
68.34
14.17
1.80
68.79
14.40
1.83
69.24
14.62
1.85
69.58
14.79
1.88
70.03
15.02
1.91
70.48
15.24
1.93
70.82
15.41
1.95
71.27
15.64
1.98
71.61
15.81
2.00
72.06
16.03
2.02
72.40
16.20
2.05
72.74
16.37
2.08
73.29
16.65
Supply
Supply Air
2.
Air
Morning
Reset
Pressure
Warm-up
Setpoint
Deadband
Setpoint
Outdoor
J7-7,8
J7-9,10
J7-11,12
"WC
Deg F
Deg F
0.42
66.89
42.24
0.43
67.38
43.45
0.44
67.78
44.45
0.45
68.18
45.46
0.46
68.59
46.47
0.47
68.99
47.47
0.48
69.39
48.48
0.49
69.80
49.49
0.50
70.20
50.50
0.52
70.60
51.50
0.53
71.00
52.51
0.53
71.33
53.32
0.54
71.73
54.32
0.56
72.25
55.62
0.57
72.81
57.03
0.58
73.26
58.16
0.60
73.83
59.57
0.61
74.28
60.70
0.62
74.73
61.82
0.63
75.18
62.95
0.64
75.63
64.08
0.65
76.08
65.21
0.67
76.65
66.62
0.67
76.99
67.46
0.69
77.44
68.59
0.70
77.89
69.72
0.71
78.34
70.85
0.72
78.79
71.98
0.73
79.24
73.10
0.74
79.58
73.95
0.75
80.03
75.08
0.76
80.48
76.21
0.77
80.82
77.05
0.78
81.27
78.18
0.79
81.61
79.03
0.80
82.06
80.15
0.81
82.40
81.00
0.82
82.74
81.85
0.83
83.29
83.23
Supply Air
Reset
RTAM
Setpoint
Supply Air
Zone or
Heat
Return Air
Setpoint
J7-11,12
J7 - 13, 14
Deg F
Deg F
66.89
86.9
67.38
88.3
67.78
89.4
68.18
90.5
68.59
91.6
68.99
92.7
69.39
93.9
69.80
95.0
70.20
96.1
70.60
97.2
71.00
98.3
71.33
99.2
71.73
100.4
72.25
101.8
72.81
103.4
73.26
104.6
73.83
106.2
74.28
107.4
74.73
108.7
75.18
109.9
75.63
111.2
76.08
112.5
76.65
114.0
76.99
115.0
77.44
116.2
77.89
117.5
78.34
118.7
78.79
120.0
79.24
121.2
79.58
122.2
80.03
123.4
80.48
124.7
80.82
125.6
81.27
126.9
81.61
127.8
82.06
129.1
82.40
130.0
82.74
130.9
83.29
132.5
RT-SVD03G-EN