Storage Environment; Agency Listing/Compliance; Factory Default Temperature Setpoints - Trane Tracer ZN517 Installation And Operation Manual

Unitary controller
Table of Contents

Advertisement

Chapter 1 Overview and specifications
4

Storage environment

If you are storing a Tracer ZN517 unitary controller for a substantial
amount of time, store it in an indoor environment that meets the
following requirements:
Temperature: From –40° to 185°F (–40° to 85°C)
Relative humidity: From 5–95%, noncondensing

Agency listing/compliance

CE—Immunity: EN50082-2:1995
EN61000-6-2:1999
CE—Emissions: EN61000-3-2:1995
EN61000-3-3:1995
EN50081-1:1992 (CISPR 22)
EN55011:1998, Class B
UL and C-UL 916 listed:
Energy management equipment
UL 94-5V (UL flammability rating for plenum use)
FCC Part 15, Class A, CFR 47

Factory default temperature setpoints

The Tracer ZN517 unitary controller relies on a number of temperature
setpoints to control HVAC equipment. Table 1 gives the factory defaults
for these setpoints, which can all be edited with the Rover service tool or a
BAS.
Table 1. Factory default temperature setpoints
Setpoints
Default setpoints
Occupied cooling
Occupied standby cooling
Unoccupied cooling
Occupied heating
Occupied standby heating
Unoccupied heating
Occupied setpoint limits
Cooling setpoint high limit
Cooling setpoint low limit
Factory defaults
°F (°C)
74.0°F (23.3°C)
78.0°F (25.6°C)
85.0°F (29.4°C)
71.0°F (21.7°C)
67.0°F (19.4°C)
60.0°F (15.6°C)
110.0°F (43.3°C)
40.0°F (44.4°C)