Trane ReliaTel Diagnostic Manual page 154

Microprocessor controls
Hide thumbs Also See for ReliaTel:
Table of Contents

Advertisement

Voyager Commercial 27½ to 50 Tons CV and VAV
Figure 86. RTAM module
VAV w/ o I GV
For remote setpoint cut this jumper:
Supply Air Pressure Setpoint R64
Supply Air Cooling Setpoint R69
Supply Air Heating Setpoint R75
Supply Air Reset Amount R68
Supply Air Pressure Deadband R67
Morning Warm-up Setpoint R63
Supply Air Reset Setpoint R66
Note: Remote SA Cooling Setpoint can be installed on RTAM J7-2, 3 (as shown) or on RTRM J6-
Morning Warm-up:
Unoccupied Heating:
Supply Air Heating
40-150 deg F +/- 2 deg F
5 Minute Changeover Heat/Cool Input
Changeover input required
154
1
2
I GV - OFF OFF
V FD - ON OFF
OFF ON
ON ON
3
4
No Reset
OFF OFF
Return A ir
OFF ON
Zone Temp ON OFF
Outdoor A i r ON ON
5
DW U D i s a bl e O FF
DW U E na b l e ON
DIP switch
12345
O N
1
2
3
4
5
SW1
Supply Air (Static) Pressure S.P .
Supply Air Cooling Setpoint
Supply Air Reset Amount
Supply Air (Static) Pressure Deadband
Morning Warmup Setpoint
Supply Air Reset Setpoint
Supply Air Heating Setpoint
2, 3. If the SA Cooling Setpoint is installed on RTRM J6-2, 3 or a BAYSENS021* is being used;
see VAV Supply Air Cooling remote setpoint - BAYSENS021*.
Is allowed even if DWU is disabled.
Enabled by transition from unocc to occup (power reset, emergency reset will not do it)
Is allowed even if DWU is disabled
Static
pressure
setpoint
Supply Air Heating
Setpoint
R 75
Supply air
Morning
cooling
warmup
setpoint
setpoint
R69
R63
1 2 3 4 5 6 7 8 9 10 11 12
SW1
LTB-S
Changeover input (VAV only)
1
2
Static
pressure
J5
deadband
For remote deadband cut
R64
R67
Reset
setpoint
R66
Reset
amount
R68
13 14
this jumper
Remote setpoint
terminal strip
RT-SVD03G-EN