Table 14. Odyssey Independent Circuit Heat Pump Units 15-20 Ton
Step
Mode
IDM
1
Fan On
On
2*
Econ.
On
3
Cool 1
On
4
Cool 2
On
5
Heat 1
On
6
Heat 2
On
7*
Heat 3
On
8*
Heat 4
On
9**
Defrost
On
10
Em. Heat On
*With Optional Accessory
**Defrost cycle in test mode runs for at least 1 minute, up to 10 minutes, depending on outdoor ambient and outdoor coil temperature.
Steps for optional accessories and modes not present in unit will be skipped.
Table 15. Gas/Electric Units 3-25 Ton
Step
Mode
IDM
1
Fan On
On
2*
Econ.
On
3
Cool 1
On
4
Cool 2
On
5
Cool 3
On
6*
Reheat
On
7*
Heat 1
On
8*
Heat 2
On
* With Optional Accessory
** "Off" if OAT falls below 60°F, "On" if OAT rises above 65°F. During Reheat, if the unit is configured with 1 compressor, ODM2 is "Off" if the OAT falls
below 70F, "On" if the OAT rises above 75F.
1. CPR2 ON during Cool 1 if configured for 3-Step Cooling; CPR1 OFF.
2. CPR2 OFF during Cool 2 on a 3-Step Cooling unit.
Steps for optional accessories and modes not present in unit will be skipped.
Table 16. Voyager Commercial VAV Service Test with Reheat and Statitrac