Wiring And Configuration - Omron DeviceNet DST1 Series Operation Manual

Safety i/o terminals
Hide thumbs Also See for DeviceNet DST1 Series:
Table of Contents

Advertisement

7-1 Wiring and Configuration

7-1
Wiring and Configuration
The following table shows input device connection methods and configuration.
Connected
device
Reset switch
Connect the switch between IN0 and T0.
Connect the switch between 24V DC and IN0.
Emergency
Connect the switches between IN0 and T0, and IN1
stop switch
and T1.
Door monitor
Connect the switches between T0 and IN0, IN.
Connect the switches between 24 V DC and IN0,
IN1.
Safety
Connect OSSD1 and OSSD2 to IN0 and IN1,
Light Curtain
respectively.
7-2
Schematic diagram
IN0
T0
IN1
T1
IN0
T0
IN1
T1
24V
IN0
T0
IN1
T1
IN0
T0
IN1
T1
IN0
T0
IN1
T1
24V
IN0
T0
IN1
T1
Configuration
Safety Input used as "Single Channel input" without
test output.
Test output used as power supply output.
Safety Input used as "Single Channel input" without
test output.
Safety Inputs used as "Dual Channel input" with test
output.
Test outputs used as "Pulse Test Output".
Safety Inputs used as "Dual Channel input" with test
output.
Test output used as "Pulse Test Output".
Safety Inputs used as "Dual Channel input" without
test output.
Safety Inputs used as "Dual Channel input" without
test output.